Vent Testing

Embers Out Elite Vents are approved and listed by the California Department of Forestry & Fire Protection through the Office of the State Fire Marshal Fire Engineering - Building Materials Listing Program. The Gable, Soffit, and Foundation Vents meet California building code SFM12-7A and are ASTM E2886/E2886M-14 certified. Ember Out Filters are designed to meet these same building specifications. 

 

In July 2014 the ASTM Fire Standards Committee approved standards for ember and direct flame impingement of exterior vents.  In July 2014 the ASTM Fire Standards Committee approved standards for ember and direct flame impingement of exterior vents.

Cal Fire

Listing 8165-2214:0100

Embers from wildfires, not the flames from the main body of the wildfire, are the main threat that homes must resist,” says ASTM member Stephen Quarles, senior scientist, Insurance Institute for Business & Home Safety. “ASTM E2886 will help users discriminate between the ember and flame resistance performance of vents.”

ASTM-E2886/E2886M-14 Ember Penetration Test Results*

The ASTM-E2886/E2886M-14 ember test is conducted by dropping embers created in a rotating circular drum suspended only ~18 inches from a horizontally mounted Elite Vent; in addition, the air was drawn through the testing chamber from below at a rate of 2 mph. The embers rained down on the Elite Vent for 7 to 8 minutes to see if the cotton material below the vent would singe, or worse ignite. At no time did even one hot burning or cold ember penetrate the Elite Vent and the test was repeated three times with the same results. 100% of all hot, burning, destructive embers were blocked. Embers Out Elite Vents not only passed the ember intrusion portion of the ASTM-E2886/E2886M-14 test but is the only vent to date with absolutely NO ember penetration at all.

Cylinder of Fire
Testing Chamber
Embers Raining Down
Cotton After Test
Show More

ASTM-E2886/E2886M-14 Direct Flame Impingement Test Results

TThe ASTM-E2886/E2886M-14 direct flame impingement test is conducted by exposing the Elite Vent to direct flames and a heat output of 300 kW for 10 minutes.

 

At three different intervals (30 s, 5m, and 9m 30s) a target cotton pad was placed next to the interior side of the vent to see if the vent allows heat to transfer through that would cause the cotton to ignite.

 

The test was repeated three times, and in all three tests NO IGNITION of the multiple cotton targets was observed!

Direct flame before the test
Perimeter Glowing
Applied Cotton Pad
Pad With No Charring
Show More

The ASTM-E2886/E2886M test was performed by Western Fire Center, Inc. (WFCi); Report #15057 & 15125. WFCi is an accredited laboratory (TL-180) under the International Accreditation Service (IAS). This accreditation encompasses the requirements of ISO/IEC 17025 and relevant requirements of the ISO 9000 series of standards. 

Traditional Louvered Vents Provide NO Protection!

Traditional Louver Style Vents, which are installed in the vast majority of homes, did not stop fire embers or wind-driven rain intrusion. In fact, severe ember and water penetration occurred at winds as low as 20 miles per hour. Since wildfires can create their own weather pattern with winds speeds up to 10 times faster than the ambient wind and a tropical storm averages 39–73 miles per hour, louver vents provide no protection from these common events!

Ember Penetration Test Result with Traditional Louvered Vent

NOTE, these are not test results of EO Vents, but rather traditional vents installed on millions of homes today.

A test wall was mounted in a vertical position on an elevated platform with two standard louvered attic vents mounted with the vents exterior side facing a flame. Burning embers were then generated and blown at the exterior side of the wall at an average wind speed of 20 mph for 7 minutes. The interior sides of the attic vents were continuously observed for the 7 minute period and any burning embers passing through the vents noted. At the end of the test the standard louvered attic vents were seen to have severe ember penetration through the vents and the embers remained lit after exiting the vents.

Water Penetration Test Results with Traditional Louvered Vent 

NOTE, these are not test results of EO Vents, but rather traditional vents installed on millions of homes today.

A test wall was mounted in a vertical position on an elevated platform with two standard louvered attic vents mounted with the vents exterior side facing the water spray. Water was then blown into the attic vents at an average spray rate of 4 gallons per hour per square foot along with an average wind speed of 20 mph. The water spray and wind speed was maintained for a period of 15 minutes during which time the interior sides of the attic vents were observed for water penetration.  During the test substantial water penetration was observed through the standard louvered attic vents.

*The Elite Vent passed the ASTM-E2886 / E2886M-14 ember test with 100% of hot and cold embers unable to penetrate the vent. In addition, the Elite Stainless Steel Vent was exposed to direct flames and passed the fire impingement portion of the ASTM International Standard Test Method for Evaluating the Ability of Exterior Vents to Resist the Entry of Embers and Direct Flame Impingement: ASTM-E2886 / E2886M-14 Testing.

PROTECT YOUR HOME FROM DESTRUCTIVE ELEMENTS LIKE WILDFIRE, MOISTURE, & PESTS

CALL OR EMAIL US 

21520 Yorba Linda Blvd, Yorba Linda, CA 92887 george@embersout.com  |  Tel: 1 (714) 363-3459

  • White Instagram Icon
  • White YouTube Icon
  • White LinkedIn Icon

EMBERS OUT, LLC:

21520 Yorba Linda Blvd.

Suite G 530 

Yorba Linda, CA  92887 

USA

CONTACT:

P: 1 (714) 363-3459

F: 1 (714) 779.3501

E: george@embersout.com

Proudly made in the USA

TERMS OF SERVICE | PRIVACY POLICY | Copyright © 2018 Embers Out, LLC All rights reserved.

Direct flame before the test